Warning
You are reading an old version of this documentation. If you want up-to-date information, please have a look at 2024.12 .Vibration timing
The effective vibration duration always corresponds to the value requested in the command. However, the duration value returned in the response depends on different conditions. The vibration timing differs from one Asycube model to the other, due to its specific electronics. For example, the Asycube 50, 80 and 240 have an activation delay of 60 ms. This section presents the most typical timing scenarios.
The activation delay corresponds to the duration between the instant when a vibration is requested and the instant when the actuators start vibrating. The activation delay is relevant for all Asycube models.
The shutdown duration corresponds to the duration between the instant when the actuators’ drivers shut down (state change from OFF to ON) and the instant when the drivers can be switched back on (state change from ON to OFF). If a vibration is triggered before or after the shutdown duration, there is no impact on the vibration. However, if a vibration is triggered during the shutdown duration, the activation only starts at the end of the shutdown duration.
The keep ON duration corresponds to the time while the actuators’ drivers stays ON after the end of the last vibration
Activation delay (A) |
Shutdown duration (B) |
Keep ON duration (C) |
|
---|---|---|---|
Asycube 50/80 |
60 ms |
180 ms |
5000 ms |
Asycube 240 |
60 ms |
180 ms |
5000 ms |
Asycube 380 |
100 ms (only for the first vibration after a power-on or a reset) |
N/A |
N/A |
Asycube 530 |
100 ms (only for the first vibration after a power-on or a reset) |
N/A |
N/A |
When a vibration/sequence is triggered, the total duration returned in the response message takes both the activation delay and the shutdown duration into account. For example, with an Asycube 50, if a vibration is triggered in the middle of the shutdown duration, the vibration will start effectively after 150 ms (60 + 180/2). This additional duration is considered in the response; for a vibration requested of 500 ms, the returned duration would be 650 ms.
Timing diagram Asycube 50, 80 and 240
The following timing diagram shows 3 vibrations triggered in different conditions:
Normal case where the actuators’ drivers are not active
During the shutdown duration
During the keep ON duration
The following timing diagram shows the case where a sequence is triggered. The actuators’ drivers stay active during the whole sequence duration with chained vibrations.
Timing diagram Asycube 380 and 530
The timing diagram of Fig. 216 shows the activation delay for the Asycube 380 and 530. The activation delay is present only for the first vibration after a power-up or a reset.